Home >> High Frequency Online UPS  

High Frequency Online UPS

Product Name:KDH-series Rack online UPS
Title:Mount type high frequency online UPS
Specifications:KDH-1KVA KDH-2KVA KDH-3KVA
Overview:
KDH Series rack online UPS power supply is a high-performance UPS designed for the user s’ integration overall engine room, small size, the structure suitable for 19 # rack cabinet installation, pure on-line design, zero interruption conversion, sine wave output, can fully resolve all power failure issues, such as mains power interruption, sustained high-voltage, voltage drop, surge distortion, clutter interference, frequency fluctuations, can be stable and reliable protection of the safe operation of the user equipment.

Description

        KDH Series rack online UPS power supply is a high-performance UPS designed for the user s’ integration overall engine room, small size, the structure suitable for 19 # rack cabinet installation, pure on-line design, zero interruption conversion, sine wave output, can fully resolve all power failure issues, such as mains power interruption, sustained high-voltage, voltage drop, surge distortion, clutter interference, frequency fluctuations, can be stable and reliable protection of the safe operation of the user equipment.

Applications
           Widely used in network-centric computer room, communications equipment control center, automation equipment overall cabinet, rail traffic signal control equipment, etc.
Technical merits
●Sine wave output
Whether in mains power mode or battery mode, the output will be low-distortion sine wave power, can provide the best power protection for the user's equipment.
●Zero conversion time
When the mains power failure or restart, UPS conversion between mains power mode and battery mode is effective as zero to ensure that the reliability of the load operation and data retention.
● Strongly engaged in interference
For electromagnetic and radio frequency interference, in accordance with international standards EN50091-2 and IEC61000-4 series of standards for the design of the UPS to effectively improve the use safety and reliability.
● Input power factor to amend
With input power factor correction, in the fully loaded case, input power factor can reach more than 0.95, which can be accessed by inductive load, and users’ grid environment will not be contaminated.
● Input live line and null line detection function
Have input live line and null line reverse connection detection function to avoid the UPS mains power input live line and null line reverse connection.
●DC power start
When the city electricity power failure, if the need to start the computer or other loading equipment, UPS can DC power start through battery, it is more convenient and reliable to use
● Automatic restart function
When the city power abnormal, the power use up at battery mode, will automatically shut down when the city power returned to normal UPS will automatically start and resume normal power supply, user don’t need to turn on the UPS one by one.
● Long-term UPS powerful charging function
Long-term models extend the discharge time, also have a strong ability to charge the battery, can provide approximately 4-9A of the initial charge current.
●Self-examination functions
Can simulate the situation of power interruption, into the battery-powered mode, This feature can carry out by self-test button on the panel at any time, also can use with electronic monitoring software to carry out at regular or irregular time.
●Can be used with generator
Input voltage and frequency range, can be used with generator, the using time will be longer,
can effectively isolate the negative power generated by the generators to provide clean, safe and stable power supply for the load
 

Main technical parameters      

Model

KDH-1KVA

KDH-2KVA

KDH-3KVA

Rated capacity

1KVA

2KVA

3KVA

Ac input

Voltage

118-300VAC

Frequency

40~60Hz(adjustable)

Input power factor

0.98

Battery

Battery voltage

DC36V

DC96V

Battery mode

VRLA maintenance free battery

Ac output

Voltage

220 VAC±1%

Frequency

50 Hz±0.05%(battery mode)

Overload capacity

110%~155%maintain35s to bypass ,155% to bypass immediately

Socket type×quantity

Multi socket×2

Transfer time

At an mode

0ms

Human -computer
interface

LED

Load indicator light, battery power light、UP running state indicator etc.

LCD

Display input, output, battery voltage, frequency, load, UPS operating parameters

Alarm sound

Battery discharge

When input voltage interrupted, every 3 seconds a call, when battery is about to exhaust, every second a call

UPS abnormal

Long time alarm

Automatic restart

Battery used up

At battery mode after mains power failure, when battery use up and mains power recover to normal, it can automatic restart

Communication interface

RS-232

Mains power abnormal、interruption、battery capacity、remote UPS turn on /off、UPS status displaying etc. intelligent monitoring function

Optional software

SNMP remote centralized monitoring card

Ambient

Temperature

0-40

Humidity

10%-90%

Machine size W×D×H(mm)

483×88×450

 

 

 

 

KDH series rack online UPS battery module:

Battery module mode

DC voltage

Weight (Kg)

Size W×H×D (mm)

KDH-1K36DC

36VDC

12.5

483×88×450

KDH-2K96DC

96VDC

25

483×88×450

KDH-3K96DC

96VDC

26

483×88×450